Protection
a) In cooling operation, protection is the same as that under the cooling mode;
b) In heating operation, protection is the same as that under the heating mode;
c) When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor will
remain unchanged for at least 6 minutes.
7.2.6 Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
Overload protection
T
tube: measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat
exchanger under heating mode.
1) Cooling overload
a) If T
tube 52°C, the unit will return to its original operation state.
b) If T
tube 55°C, frequency rise is not allowed.
c) If T
tube 58°C, the compressor will run at reduced frequency.
d) If T
tube 62 °C, the compressor will stop and the indoor fan will run at preset speed.
2) Heating overload
a) If T
tube 50°C, the unit will return to its original operation state.
b) If T
tube 53°C, frequency rise is not allowed.
c) If T
tube 56°C, the compressor will run at reduced frequency.
d) If T
tube 60°C, the compressor will stop and the indoor fan will blow residue heat and then stop.
Exhaust temperature protection of compressor
If exhaust temperature 98°C, frequency is not allowed to rise.
If exhaust temperature 103°C, the compressor will run at reduced frequency.
If exhaust temperature 110°C, the compressor will stop.
If exhaust temperature 90°C and the compressor has stayed at stop for at least 3 minutes, the compressor will resume its
operation.
Communication fault
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justified and the whole system
will stop and the display will show the error code E6.
Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the
compressor will resume its operation. If module protection occurs six times in succession, the compressor will not be started
again.
Overload protection
If temperature sensed by the overload sensor is over 115°C, the compressor will stop and the outdoor fan will stop with a
time lag of 30 seconds. If temperature is below 95°C, the overload protection will be relieved.
If voltage on the DC bus is below 150V or over 420V
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time lag of
30 seconds. When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least 3
minutes, the compressor will resume its operation.