11
7. Control functions
7.1. Temperature Parameters
Indoor preset temperature (Tpreset)
Indoor ambient temperature (T
amb)
7.2. Basic functions
Once energized, the compressor should in no way be restarted unless after at least 3-minute time interval. In case of having
memory function, for the first energization, the compressor will be started without 3-minute lag, if being under the condition
of power-off, and the compressor will have 3-minutes delay to be started under the condition of power-on. Once started, the
compressor will not be stopped within 6 minutes with the changes of room temperature.
7.2.1 Cooling Mode
Cooling Condition and Process
When T
amb. Tpreset , the unit will run under cooling mode, in which case the compressor and outdoor fan will be started,
and the indoor fan will run at preset speed.
When T
amb. Tpreset -3°C, the compressor will stop, the outdoor fan will stop with time lag of 30s, and the indoor fan will run
at preset speed.
When T
preset -3°C <Tamb. < Tpreset , the unit will maintain its original operating status.
Under this mode, the switchover (reversal) valve will be de-energized and the temperature can be set from 16°C to 30°C.
If the compressor is shut down for some reason, the indoor fan and the swing device will operate at the original state.
Tpreset
Tpreset –2 ˚C
Compressor
Outdoor fan
Indoor fan
Run
Tamb.
Stop
Stop cooling
Start cooling
Original operating status
6 min. 3 min. 6 min.
Setting fan speed
Protection function
Overcurrent protection
If total current is high, the compressor will run in limited frequency. If total current is too high, the compressor will stop, the
outdoor fan will delay 30 seconds to stop, indoor unit will display E5 and outdoor yellow light will blink 5 times.
Antifreeze protection
When the antifreeze protection is detected, the compressor will stop, the outdoor fan will stop after 30 seconds, and the
indoor fan and swing motor will keep running in the original mode. When antifreeze protection is eliminated and the
compressor has stopped for 3 minutes, the compressor will resume running in the original mode.
The period o
f
antifreezing protection
Compressor
Outdoor fan
Indoor fan
3 min
Low fan speed
Run
Stop